Inverters
AC
MAIN FEATURES
STANDARD ESPECIFICATIONS
| CONTROL | |
Control Method |
Sinusoidal PWM modulation; 2 or 3 phases modulation selectable |
Close loop control |
Quadrature input clock feed back by encoder |
Open loop control |
Panel, Potentiometer, 0VDC to 10VDC; 0VDC to 5VDC; +5VDC to -5VDC; 0mADC to 20mADC; 4mADC to 20mADC and their inverses. |
Output Frequency |
200Hz; 650Hz; 1500Hz; 3000Hz in function to versions |
Frequency setting resolution |
0.01Hz for digital input; 0.1Hz for analog input |
Frequency accurancy |
+/-0.01Hz |
Volt/Freq characteristics |
from linear to parabolic curve programable |
Computer interface |
Built-in RS-485 communication port allows settings and date control. Up 99 unit inverters can be put under centralized control of computer. |
Multi-function digital input |
4 photo-coupler input terminals are all designed as programmable input terminal |
Multi-function analog input |
2 programmable terminals. The first by tension (10V; +/-5V); the second by signal (+5V; 20mADC) |
Frequency Skip |
Setting skip frequency and width |
PWM carry frequency |
Programable in the range of 2kHz to 16kHz |
Upper/Lower limit frequency |
Programable upper/lower limit frequency |
| OPERATING FUNCTION | |
Acceleration/deceleration time |
0.1 to 6553 sec. and selection soft acceleration/deceleration |
Regenerative discharge braking |
Built-in or external as option in function versions. |
DC injection braking |
Injection start frequency, braking voltage and time all programmable |
Automatic restart |
Speed searching to recover a FREE RUN motor. |
Multi-function digit output |
2 terminals are open collector output. 2 terminals are Normal open contact relay output. Any of the above outputs are programable. |
Multi-function analog output |
Selectable output for analog meter: Hz; Irms; VDC; Vout (1V/1mADC) |
Voltage boost |
Programable voltage boost level from 0% to 30% |
Output voltage regulation |
Enable/Disable setting by software |
Automatic step run |
Step running by 5-speed setting, 5-acc/dec, time, 5-period time and 5-auto mode. |
Multi-speed run |
With the combinations of the 4 digit input 5 speed levels can be selected |
| PROTECTIONS | |
Short-circuit protection |
Between output phases (U-V-W); Between output phases and earth (Optional) |
Momentary power interrupt |
Programable restart function |
Stall prevention |
Programable stall current level from 10% to 200% |
Over load current |
Adjustable up to 200% |
Motor rating |
Setting 10% to 100% of inverter rating |
Over voltage |
130% of line voltage |
Under voltage |
70% of line voltage |
Over temperature |
Fin over heat and external over heat input |
| DISPLAY | |
Multi-function monitor display |
Hz, RPM, VDC input, Vrms, Irms and terminals status |
Alarm indications |
Over voltage, Under voltage, Over load, Over heat, Over current, Communication error, Alarm history |
Status indications |
Forward, Reverse, Hz, I |
| INSTALATION | |
Service enviroment |
Indoor, Altitud 1000 m (3300 ft) maximum. Must not be exposed to direct sunlight or subject to corrosive or flammable gases or fluids. |
Temperature |
from -10ºC to +40ºC |
Relative humidity |
90% maximum (no condensation allowed) |
Vibration |
Acceleration at 0.5G maximum (20Hz to 50Hz); Amplitude at 0.1mm maximum (50Hz to 100Hz) |